Energy infrastructure

Power for AI.

How wind generation, battery storage and flexible compute can share a constrained grid connection.

Explore campus dispatch
Reference campus demand
100 MW
Battery power / nominal energy
50 MW / 200 MWh

Campus dispatch

Compare three illustrative operating conditions. Each holds wind availability and the grid limit constant for the duration shown.

Facility power balance

2-hour operating window

Campus demand
100 MW
Wind supplied
45 MW
Grid import
30 MW
Battery discharge
25 MW
  • Wind
  • Grid
  • Battery

Demand covered. The battery delivers 50 MWh over 2 hours.

From generation to compute

Wind power

Wind output is measured at the site bus after wake, availability and electrical losses. Available generation serves campus load first.

Dispatch assumptions

The campus starts with a 100 MW facility load, including cooling. Flexible compute can reduce demand in the low-wind case. Wind and utility power meet demand before the battery discharges. The model caps battery output at 50 MW and limits discharge to 160 MWh of usable AC energy over the operating window. It does not model charging, transients or changes within an hour.